Backflow assembly test: Blue Heron Taqueria

Approved

Filed Feb 26, 2025 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 26, 2025
Assembly type
RP
Serial number
B579787
Size
1
Test gauge serial
G-6563
Gauge calibration date
Sep 4, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-38-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4098 Cedar Hollow Trl
Owner: Whitcomb Holdings LLC
Parcel 055-38-01327