Backflow assembly test: Blue Heron Taqueria
ApprovedFiled Mar 30, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 30, 2026
- Assembly type
- RP
- Serial number
- B579787
- Size
- 1
- Test gauge serial
- G-5326
- Gauge calibration date
- Oct 20, 2025
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Calloway, current on the service date
- All required fields present
- Address matches parcel 055-38-01327
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.