Backflow assembly test: Blue Heron Taqueria

Approved

Filed Mar 30, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 30, 2026
Assembly type
RP
Serial number
B579787
Size
1
Test gauge serial
G-5326
Gauge calibration date
Oct 20, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-38-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4098 Cedar Hollow Trl
Owner: Whitcomb Holdings LLC
Parcel 055-38-01327