Back to the backflow review queue
Backflow assembly test: 1713 Pine Knoll Rd
ApprovedFiled Apr 25, 2026 by Hayden Fairley, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 25, 2026
- Assembly type
- RP
- Serial number
- W608964
- Size
- 3/4
- Test gauge serial
- G-2892
- Gauge calibration date
- Nov 28, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Fairley, current on the service date
- All required fields present
- Address matches parcel 055-30-01101
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1713 Pine Knoll Rd
Owner: Avery Lindqvist
Parcel 055-30-01101