Back to the backflow review queue
Backflow assembly test: 798 Quarry Rd
ApprovedFiled May 18, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- May 18, 2025
- Assembly type
- RP
- Serial number
- A136386
- Size
- 3/4
- Test gauge serial
- G-6823
- Gauge calibration date
- Jan 13, 2025
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Brandt, current on the service date
- All required fields present
- Address matches parcel 055-90-01199
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
798 Quarry Rd
Owner: Riley Marsh
Parcel 055-90-01199