Backflow assembly test: 7268 Laurel Trl
ApprovedFiled Jun 6, 2024 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 6, 2024
- Assembly type
- DC
- Serial number
- W538133
- Size
- 3/4
- Test gauge serial
- G-7271
- Gauge calibration date
- Nov 9, 2023
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Calloway, current on the service date
- All required fields present
- Address matches parcel 055-17-01232
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.