Back to the backflow review queue

Backflow assembly test: 8610 Hickory Trl

Approved

Filed Jun 15, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 15, 2026
Assembly type
DC
Serial number
B575444
Size
3/4
Test gauge serial
G-6443
Gauge calibration date
Oct 20, 2025
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-88-01080
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8610 Hickory Trl
Owner: Morgan Nguyen
Parcel 055-88-01080