Backflow assembly test: Blue Heron Pizza
ApprovedFiled Oct 8, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 8, 2026
- Assembly type
- DC
- Serial number
- A446953
- Size
- 2
- Test gauge serial
- G-4998
- Gauge calibration date
- Jun 4, 2026
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Calloway, current on the service date
- All required fields present
- Address matches parcel 055-41-01255
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.