Backflow assembly test: 4464 Turkey Hill Dr
ApprovedFiled Aug 21, 2024 by Avery Ramirez, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 21, 2024
- Assembly type
- RP
- Serial number
- A435504
- Size
- 3/4
- Test gauge serial
- G-4809
- Gauge calibration date
- Nov 5, 2023
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 059-86-01284
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4464 Turkey Hill Dr
Owner: Taylor Harlow
Parcel 059-86-01284