Back to the backflow review queue

Backflow assembly test: Crossroads Market

Approved

Filed Aug 19, 2024 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 19, 2024
Assembly type
RP
Serial number
Z219039
Size
1 1/2
Test gauge serial
G-7535
Gauge calibration date
Jan 11, 2024
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-85-01344
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2600 Orchard Rd
Owner: Marsh Holdings LLC
Parcel 059-85-01344