Backflow assembly test: 4337 Old Church Trl

Approved

Filed Jun 21, 2026 by Riley Calloway, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 21, 2026
Assembly type
RP
Serial number
B247775
Size
3/4
Test gauge serial
G-4040
Gauge calibration date
Apr 9, 2026
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.3 psid
Relief valve opened at
4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-44-01292
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.