Back to the backflow review queue

Backflow assembly test: Main Street Diner

Approved

Filed Jun 6, 2024 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 6, 2024
Assembly type
DC
Serial number
B538033
Size
1
Test gauge serial
G-7945
Gauge calibration date
Sep 5, 2023
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-28-01051
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1500 Fox Run Ct
Owner: Harlow Holdings LLC
Parcel 059-28-01051