Backflow assembly test: 9131 Old Church Ln
ApprovedFiled Nov 11, 2025 by Logan Stroud, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 11, 2025
- Assembly type
- PVB
- Serial number
- A634459
- Size
- 1
- Test gauge serial
- G-1788
- Gauge calibration date
- Aug 3, 2024
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Stroud, current on the service date
- All required fields present
- Address matches parcel 059-58-01105
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.