Back to the backflow review queue

Backflow assembly test: Riverside Elementary School

Approved

Filed Jun 14, 2025 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jun 14, 2025
Assembly type
RP
Serial number
Z405569
Size
4
Test gauge serial
G-7705
Gauge calibration date
Nov 10, 2024
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 059-33-01015
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

999 Fox Run Trl
Owner: Brandt Holdings LLC
Parcel 059-33-01015