Backflow assembly test: Riverside Elementary School
ApprovedFiled Jun 2, 2026 by Riley Calloway, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jun 2, 2026
- Assembly type
- RP
- Serial number
- Z405569
- Size
- 4
- Test gauge serial
- G-5234
- Gauge calibration date
- Oct 7, 2025
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Calloway, current on the service date
- All required fields present
- Address matches parcel 059-33-01015
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
999 Fox Run Trl
Owner: Brandt Holdings LLC
Parcel 059-33-01015