Back to the backflow review queue
Backflow assembly test: 3315 Turkey Hill Dr
ApprovedFiled Jan 6, 2024 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 6, 2024
- Assembly type
- DC
- Serial number
- A697798
- Size
- 1
- Test gauge serial
- G-7173
- Gauge calibration date
- Apr 11, 2023
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 059-16-01069
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3315 Turkey Hill Dr
Owner: Morgan Calloway
Parcel 059-16-01069