Backflow assembly test: 3193 Old Church Rd

Approved

Filed Sep 11, 2026 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 11, 2026
Assembly type
RP
Serial number
K364413
Size
3/4
Test gauge serial
G-2755
Gauge calibration date
Sep 17, 2025
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
3.6 psid
Relief valve opened at
3.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-49-01109
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3193 Old Church Rd
Owner: Alex Okafor
Parcel 059-49-01109