Back to the backflow review queue

Backflow assembly test: 9128 Laurel Dr

Approved

Filed Oct 20, 2025 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 20, 2025
Assembly type
RP
Serial number
A928181
Size
1
Test gauge serial
G-6566
Gauge calibration date
Jul 3, 2025
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-55-01095
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9128 Laurel Dr
Owner: Jordan Stroud
Parcel 059-55-01095