Back to the backflow review queue

Backflow assembly test: 1372 Cedar Hollow Dr

Approved

Filed Nov 7, 2026 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 7, 2026
Assembly type
DC
Serial number
W833514
Size
3/4
Test gauge serial
G-4988
Gauge calibration date
Jun 1, 2026
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-58-01230
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1372 Cedar Hollow Dr
Owner: Taylor Fairley
Parcel 059-58-01230