Backflow assembly test: 8607 Hickory Way
ApprovedFiled Jul 12, 2024 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 12, 2024
- Assembly type
- RP
- Serial number
- Z102910
- Size
- 1
- Test gauge serial
- G-7996
- Gauge calibration date
- Mar 14, 2024
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Stroud, current on the service date
- All required fields present
- Address matches parcel 059-62-01110
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8607 Hickory Way
Owner: Emerson Nguyen
Parcel 059-62-01110