Backflow assembly test: 3101 Meadow Lark Way

Approved

Filed Mar 11, 2025 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 11, 2025
Assembly type
RP
Serial number
A516884
Size
3/4
Test gauge serial
G-7662
Gauge calibration date
Sep 19, 2024
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-68-01249
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3101 Meadow Lark Way
Owner: Taylor Stroud
Parcel 059-68-01249