Backflow assembly test: Hilltop Bakery

Approved

Filed Mar 3, 2026 by Casey Pruitt, Clearwater Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 3, 2026
Assembly type
RP
Serial number
W853224
Size
1
Test gauge serial
G-2170
Gauge calibration date
Jun 29, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 061-21-01165
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.