Backflow assembly test: Maple Leaf Pizza
ApprovedFiled Jan 4, 2024 by Alex Benton, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 4, 2024
- Assembly type
- DC
- Serial number
- A202632
- Size
- 4
- Test gauge serial
- G-2038
- Gauge calibration date
- Sep 17, 2022
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 061-11-01185
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.