Back to the backflow review queue

Backflow assembly test: 8699 Laurel Trl

Approved

Filed Jun 23, 2025 by Jamie Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jun 23, 2025
Assembly type
RP
Serial number
B275804
Size
3/4
Test gauge serial
G-8290
Gauge calibration date
Nov 16, 2024
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Kessler, current on the service date
  • All required fields present
  • Address matches parcel 061-75-01071
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8699 Laurel Trl
Owner: Riley Brandt
Parcel 061-75-01071