Backflow assembly test: 3078 Meadow Lark Rd

Approved

Filed Jan 9, 2025 by Jamie Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jan 9, 2025
Assembly type
RP
Serial number
A394491
Size
3/4
Test gauge serial
G-6811
Gauge calibration date
Jul 16, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Kessler, current on the service date
  • All required fields present
  • Address matches parcel 061-26-01188
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.