Backflow assembly test: 6381 Hickory Trl

Approved

Filed Jul 13, 2023 by Taylor Ashby, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 13, 2023
Assembly type
DC
Serial number
Z280154
Size
1
Test gauge serial
G-9063
Gauge calibration date
Nov 24, 2022
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Ashby, current on the service date
  • All required fields present
  • Address matches parcel 061-38-01019
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6381 Hickory Trl
Owner: Avery Ashby
Parcel 061-38-01019