Back to the backflow review queue

Backflow assembly test: 1681 Meadow Lark Rd

Approved

Filed Mar 8, 2025 by Quinn Nguyen, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 8, 2025
Assembly type
DC
Serial number
Z781740
Size
3/4
Test gauge serial
G-1028
Gauge calibration date
Dec 12, 2023
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 065-22-01136
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1681 Meadow Lark Rd
Owner: Parker Wexler
Parcel 065-22-01136