Backflow assembly test: 8464 Old Church Ct

Approved

Filed Jun 23, 2026 by Morgan Wexler, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 23, 2026
Assembly type
DC
Serial number
A203493
Size
1
Test gauge serial
G-2047
Gauge calibration date
Apr 21, 2026
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-20-01232
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8464 Old Church Ct
Owner: Quinn Pruitt
Parcel 065-20-01232