Backflow assembly test: 8812 Mill Creek Ct

Approved

Filed Feb 16, 2024 by Quinn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 16, 2024
Assembly type
RP
Serial number
B240787
Size
3/4
Test gauge serial
G-6781
Gauge calibration date
May 30, 2023
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 065-85-01084
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8812 Mill Creek Ct
Owner: Blake Okafor
Parcel 065-85-01084