Backflow assembly test: 159 Ridgeview Ln
ApprovedFiled Jul 3, 2024 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 3, 2024
- Assembly type
- RP
- Serial number
- K625718
- Size
- 3/4
- Test gauge serial
- G-9055
- Gauge calibration date
- Feb 6, 2024
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 065-39-01201
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.