Backflow assembly test: 7313 Fox Run Dr

Approved

Filed Jul 20, 2024 by Alex Wexler, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 20, 2024
Assembly type
RP
Serial number
A167394
Size
3/4
Test gauge serial
G-5285
Gauge calibration date
Mar 16, 2024
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-48-01266
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.