Back to the backflow review queue

Backflow assembly test: 4792 Hickory Ct

Approved

Filed Jan 10, 2026 by Quinn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 10, 2026
Assembly type
DC
Serial number
W150736
Size
1
Test gauge serial
G-4527
Gauge calibration date
Nov 19, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 065-97-01191
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4792 Hickory Ct
Owner: Riley Danner
Parcel 065-97-01191