Back to the backflow review queue

Backflow assembly test: Maple Leaf Animal Hospital

Approved

Filed Sep 13, 2025 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 13, 2025
Assembly type
RP
Serial number
W302448
Size
1 1/2
Test gauge serial
G-1495
Gauge calibration date
Jun 27, 2025
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 065-52-01356
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6154 Hickory Trl
Owner: Wexler Holdings LLC
Parcel 065-52-01356