Backflow assembly test: Hilltop Dental
ApprovedFiled May 29, 2024 by Blake Harlow, Evergreen Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 29, 2024
- Assembly type
- RP
- Serial number
- A209659
- Size
- 4
- Test gauge serial
- G-9238
- Gauge calibration date
- Dec 12, 2023
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Harlow, current on the service date
- All required fields present
- Address matches parcel 065-12-01178
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3468 Orchard Ln
Owner: Harlow Holdings LLC
Parcel 065-12-01178