Backflow assembly test: Hilltop Medical Offices

Approved

Filed Jun 5, 2026 by Reese Calloway, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jun 5, 2026
Assembly type
RP
Serial number
A794799
Size
1
Test gauge serial
G-6640
Gauge calibration date
Mar 22, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 065-41-01355
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2995 Ridgeview Trl
Owner: Calloway Holdings LLC
Parcel 065-41-01355