Back to the backflow review queue

Backflow assembly test: 9720 Old Church Way

Approved

Filed May 6, 2026 by Morgan Wexler, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 6, 2026
Assembly type
RP
Serial number
A406761
Size
3/4
Test gauge serial
G-4019
Gauge calibration date
Dec 16, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-40-01235
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9720 Old Church Way
Owner: Logan Nguyen
Parcel 065-40-01235