Backflow assembly test: 7920 Laurel Dr

Approved

Filed Jun 22, 2025 by Reese Calloway, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jun 22, 2025
Assembly type
RP
Serial number
K811205
Size
1
Test gauge serial
G-5338
Gauge calibration date
Mar 24, 2025
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 065-20-01206
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7920 Laurel Dr
Owner: Reese Calloway
Parcel 065-20-01206