Back to the backflow review queue

Backflow assembly test: Blue Heron Grill

Approved

Filed Jan 23, 2026 by Reese Lindqvist, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 23, 2026
Assembly type
RP
Serial number
K402706
Size
4
Test gauge serial
G-2545
Gauge calibration date
May 14, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 065-54-01074
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7621 Spring Branch Rd
Owner: Ashby Holdings LLC
Parcel 065-54-01074