Back to the backflow review queue
Backflow assembly test: Blue Heron Grill
ApprovedFiled Jan 23, 2026 by Reese Lindqvist, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 23, 2026
- Assembly type
- RP
- Serial number
- K402706
- Size
- 4
- Test gauge serial
- G-2545
- Gauge calibration date
- May 14, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Lindqvist, current on the service date
- All required fields present
- Address matches parcel 065-54-01074
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7621 Spring Branch Rd
Owner: Ashby Holdings LLC
Parcel 065-54-01074