Back to the backflow review queue
Backflow assembly test: Hilltop Elementary School
ApprovedFiled Aug 20, 2026 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 20, 2026
- Assembly type
- RP
- Serial number
- B557280
- Size
- 1
- Test gauge serial
- G-1484
- Gauge calibration date
- Jul 15, 2026
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 065-76-01331
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6831 Meadow Lark Ln
Owner: Whitcomb Holdings LLC
Parcel 065-76-01331