Backflow assembly test: 3431 Laurel Ct

Approved

Filed Jul 21, 2026 by Blake Harlow, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 21, 2026
Assembly type
RP
Serial number
B870467
Size
3/4
Test gauge serial
G-8503
Gauge calibration date
Jun 15, 2026
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Harlow, current on the service date
  • All required fields present
  • Address matches parcel 065-58-01350
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3431 Laurel Ct
Owner: Logan Benton
Parcel 065-58-01350