Back to the backflow review queue

Backflow assembly test: 7330 Spring Branch Dr

Approved

Filed Aug 19, 2026 by Blake Brandt, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 19, 2026
Assembly type
RP
Serial number
Z937926
Size
3/4
Test gauge serial
G-6028
Gauge calibration date
Jun 8, 2026
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Brandt, current on the service date
  • All required fields present
  • Address matches parcel 065-47-01085
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7330 Spring Branch Dr
Owner: Casey Calloway
Parcel 065-47-01085