Backflow assembly test: 4748 Mill Creek Ct
ApprovedFiled Apr 29, 2025 by Blake Harlow, Evergreen Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 29, 2025
- Assembly type
- RP
- Serial number
- W811845
- Size
- 3/4
- Test gauge serial
- G-1681
- Gauge calibration date
- Jul 5, 2024
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Harlow, current on the service date
- All required fields present
- Address matches parcel 065-99-01163
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.