Back to the backflow review queue

Backflow assembly test: 2645 Stone Gate Way

Approved

Filed Aug 1, 2024 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 1, 2024
Assembly type
RP
Serial number
B772545
Size
3/4
Test gauge serial
G-6236
Gauge calibration date
Feb 27, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 065-62-01290
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2645 Stone Gate Way
Owner: Jordan Ellery
Parcel 065-62-01290