Backflow assembly test: 9442 Cedar Hollow Way

Approved

Filed Nov 14, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 14, 2024
Assembly type
DC
Serial number
Z805617
Size
1
Test gauge serial
G-6402
Gauge calibration date
Jul 9, 2023
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-50-01132
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.