Backflow assembly test: Station Medical Offices

Approved

Filed Sep 13, 2024 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 13, 2024
Assembly type
RP
Serial number
B376140
Size
1
Test gauge serial
G-9013
Gauge calibration date
Feb 11, 2024
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-64-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1662 Spring Branch Trl
Owner: Benton Holdings LLC
Parcel 067-64-01147