Backflow assembly test: 2051 Fox Run Dr

Approved

Filed Apr 21, 2025 by Avery Benton, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 21, 2025
Assembly type
RP
Serial number
W319767
Size
3/4
Test gauge serial
G-1492
Gauge calibration date
May 6, 2024
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Benton, current on the service date
  • All required fields present
  • Address matches parcel 067-83-01299
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.