Backflow assembly test: 6296 Orchard Ct
ApprovedFiled Jun 26, 2023 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 26, 2023
- Assembly type
- RP
- Serial number
- A926653
- Size
- 3/4
- Test gauge serial
- G-4928
- Gauge calibration date
- Apr 5, 2023
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-14-01283
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.