Backflow assembly test: Main Street Pizza
ApprovedFiled May 1, 2025 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 1, 2025
- Assembly type
- RP
- Serial number
- W132709
- Size
- 1 1/2
- Test gauge serial
- G-3419
- Gauge calibration date
- Feb 3, 2025
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 067-58-01215
- Readings in range, no flags
- Result: passing. Next due date resets when approved.