Back to the backflow review queue
Backflow assembly test: 8128 Pine Knoll Ct
ApprovedFiled Nov 3, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 3, 2024
- Assembly type
- DC
- Serial number
- B914682
- Size
- 1
- Test gauge serial
- G-3911
- Gauge calibration date
- Mar 13, 2024
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-65-01182
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8128 Pine Knoll Ct
Owner: Taylor Kessler
Parcel 067-65-01182