Backflow assembly test: 3194 Ridgeview Trl
ApprovedFiled Oct 21, 2026 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 21, 2026
- Assembly type
- DC
- Serial number
- W785501
- Size
- 3/4
- Test gauge serial
- G-1379
- Gauge calibration date
- Jan 18, 2026
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Danner, current on the service date
- All required fields present
- Address matches parcel 067-74-01123
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.