Backflow assembly test: Hilltop Diner

Approved

Filed Jan 9, 2024 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 9, 2024
Assembly type
RP
Serial number
K348905
Size
1
Test gauge serial
G-8643
Gauge calibration date
Mar 21, 2023
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-70-01241
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.